What ΔT is considered a critical electrical fault?

Electrical thermographyPublished 14 August 2026Reviewed 9 September 2026

The short answer

A temperature difference greater than 30 °C against an identical reference component, or a fault temperature above 100 °C, is rated Priority 1 — Critical: a serious abnormality where immediate repair is recommended. Below that, 20–30 °C is Priority 2 (repair within a week), 10–20 °C is Priority 3 (rectify when convenient and re-inspect), and under 10 °C is Priority 4 — no abnormality at the time of inspection.

Why there are two different numbers

Every finding is measured two ways, and the worse of the two sets the rating.

The temperature difference — phase B against phase A on the same board, under the same load — is the more sensitive measure, because both components should be doing identical work. If one is hot and its twin is not, the cause is the component rather than the duty.

The absolute fault temperature is the backstop. A connection at 110 °C is dangerous whether or not its neighbours are hot too, and it is the only measure available when there is no equivalent component to reference.

This is why a report that quotes a single temperature is not a finding. 91 °C on a lug means nothing until you know what the other two phases were doing.

The priority ratings in full

PriorityΔT vs referenceFault temperatureRecommended action
1 — Critical> 30 °C> 100 °CSerious abnormality. Immediate repair recommended — failure may be imminent.
2 — Significant20 – 30 °C75 – 100 °CShould be corrected — could fail suddenly. Repair within one week.
3 — Caution10 – 20 °C50 – 75 °CMinor problem. Rectify when convenient, then re-inspect for the trend.
4 — Checked< 10 °C< 50 °CNo abnormality at inspection. Re-inspect at regular intervals.

What can make the number wrong

  • Load below 40%. A fault under light load may not generate enough heat to register. This is the most common reason a real defect is missed.
  • Emissivity error. Shiny copper and painted steel emit very differently; an uncorrected reading on bare copper can be out by tens of degrees.
  • Reflection. Polished surfaces mirror the thermographer, the lighting and the camera, producing hot spots that are not there.
  • Spatial resolution. If the target is smaller than the camera's measurement spot, the reading averages it with everything around it — always low.

Every one of those errors runs in the same direction: the component reads cooler than it is.

Frequently asked

Is 60 °C on a switchboard connection dangerous?

It depends on what sits beside it. If the other phases are at 55 °C that is normal load heating, and the fault temperature alone puts it in Priority 3. If they are at 25 °C, the 35 °C difference makes it Priority 1 — immediate repair.

Who is qualified to classify a finding?

A Category 2 thermographer certified to ISO 18436-7 or equivalent. A Category 1 holder can capture images; setting and applying criteria is a Category 2 function.

Written by the team that does the work — ISO 18436-7 Category 2 thermography, IRATA Level 3 rope access and QBCC licensed waterproofing. If your situation does not match anything above, call and describe it; we will tell you straight away whether we are the right people for it.

Keep reading

Related articles.

Knowledge base
Electrical thermography

Diagnosing Electrical Problems Safely With Thermal Imaging

Thermal imaging diagnoses electrical faults without contact, from outside the arc flash boundary, on equipment that stays live and loaded. The accuracy of what it tells you depends almost entirely on the surface being measured: emissivity, reflection and the size of the target against the camera's measurement spot will each shift a reading, and all three shift it in the same direction — too low. Understanding the surface is what separates a measurement from a picture.

Electrical thermography

3 Ways Infrared Thermography Improves Electrical Maintenance

Infrared thermography improves electrical maintenance in three ways: it finds developing faults while equipment is still running, so repairs are planned rather than forced; it produces measured evidence that lets you rank work by severity instead of guessing; and repeated over time it establishes trends, which turns a list of findings into a maintenance programme that predicts failure rather than reacting to it.

Electrical thermography

Electrical Thermography Benefits for Building Managers

For a building manager, electrical thermography converts an unpredictable risk into a scheduled line item. It surveys main and tenancy distribution boards without an outage, produces a documented condition record for the building's asset register, satisfies the annual inspection condition most insurers now attach at renewal, and gives a defensible answer to a committee or owner asking whether the electrical infrastructure is safe.